ZTE ZXDU68 S601 communication power supply system cabinet set
Product parameters:
Applicable environment:
Working temperature: - 5 ℃ ~ + 45 ℃, optimum + 15 ℃ ~ + 25 ℃
Storage temperature: - 40 ℃ ~ + 70 ℃
Relative humidity: 10% - 90% (non condensing), best 40% - 60%
Atmospheric pressure: 70 kPa ~ 106 kPa
AC distribution:
AC input system three phase five wire system (L1 / L2 / L3 / N / PE)
Rated AC input voltage, phase voltage: 220 V, line voltage: 380 V
AC input voltage range fluctuation range (phase voltage): 80 V ~ 300 V
When l < 70 V, under voltage shutdown;
When 70 V ~ 80 V, under voltage protection;
When 80 V ~ 100 V, the current limiting point of single rectifier is 20a ± 2A;
When 100 V ~ 176 V, the current limiting point of single rectifier is 31a ± 2A;
When 176 V ~ 300 V, the current limiting point of single rectifier is 53a ± 1a;
At 300 V, the over-voltage protection is shut down
AC input frequency range: 50 / 60 Hz
Single phase maximum input current: 72 A
Lightning protection level C: AC lightning protection, lightning discharge current ≤ 40 Ka
Input power factor: ≥ 0.99
DC distribution
Rated DC output voltage: - 53.5 V
Adjustable range of DC output voltage: - 42 V ~ - 58 V
Rated output current: 600 a (full configuration)
Maximum output power: 34800 w (full configuration)
Overall efficiency: ≥ 91%
Source effect: ≤ 0.1%
Load effect: ≤ 0.5%
Voltage stabilization accuracy: ≤ 0.6%
Structural parameters:
Cabinet color (Pantone) ZTE light grey
Cabinet size: 1600 mm (H) x 600 mm (W) x 400 mm (d)
Cabinet weight: 85 kg (including monitoring unit and excluding rectifier)
Single circuit triple 100A input (AC) with DC lightning protection
Battery: 400A * 2 channels
One power down:
Fuse: 100A * 4 ways
Air switch: 63A * 3, 32A * 4, 16a * 1
Secondary power down:
Air switch: 63A * 2, 32A * 2, 16a * 2, 10a * 2
Monitoring: T601
Rectifier module: up to 12 zxd2400 can be equipped